SPECIFICATIONS

Model

FS-V31P

Type

1-output with cable

Output

PNP

Main unit/Expansion unit

Main unit

Control output

1 output

Monitor output (1 to 5 V)

N/A

External input

Connector

Light source

Red, 4-element LED (Wavelength: 640 nm)

Response time

33 µs (HIGH SPEED) /250 µs (FINE) /500 µs (TURBO) /1 ms (SUPER TURBO) /4 ms (ULTRA TURBO) /16 ms (MEGA TURBO)

Output selection

LIGHT-ON/DARK-ON (switch-selectable)

Display indicator

Operation indicator: Red LED/Dual digital monitor: Dual 7-segment display, Preset Value (4-digit green LED indicator) and
Current Value (4-digit red LED indicator) illuminated together. Current Value range: 0 to 64,512; Excess gain: 0P to 999P,
Hold function: Possible to display both peak and bottom hold values, Selectable from 5 variations
Bar LED monitor: Excess gain displayed (85% to 115% in 7 steps), Scaling display

Detection mode

Light intensity (area detection possible, automatic sensitivity-tracking function provided)

Timer function

OFF-delay timer/ON-delay timer/One-shot timer/ON-delay timer + OFF-delay timer/ON-delay timer + One-shot timer, selectable
Timer duration selectable: 0.1 ms to 9,999 ms, Maximum error against the setting value: ±10% max.

Control output

PNP open-collector 24 V, 100 mA max.*1 (main unit only)/20 mA max. (when the expansion unit(s) is connected), Residual voltage: 1 V max.

External inputy

Input time: 2 ms (ON)/20 ms (OFF) min.*2

Unit expansion

Up to 16 expansion units can be connected (a total of 17 units). Note that the 2-output type should be counted as two units.

Number of interference prevention units

Normal operation

HIGHSPEED:0 FINE:4 TURBO/SUPER/ULTRA/MEGA:8台

Size

30.3 mm (H) x 9.8 mm (W) x 71.8 mm (D)

Rating

Power voltage

12 to 24 VDC ±10 %, Ripple (P-P) 10 % or less

Power consumption

Normal: 750 mW max. (Using 24 V, 31 mA max., using 12 V, 40 mA max.)/
Power saving 580 mW max. (Using 24 V, 24 mA max., using 12 V,
28 mA max.)*3

Environmental resistance

Ambient light

Incandescent lamp: 20,000 lux max., Sunlight: 30,000 lux max.

Ambient temperature

-10 to +55 °C (No freezing)*4

Relative humidity

35 to 85 % RH (No condensation)

Vibration resistance

10 to 55 Hz, Double amplitude 1.5 mm, 2 hours in each of the X, Y, and Z directions

Shock resistance

500 m/s2, 3 times in each of the X, Y, and Z directions

Case material

Polycarbonate

Accessories

N/A

Weight

Approx. 80 g

|

VitalMRO is not an authorized distributor, reseller or representative of the products featured on this website. All product names, trademarks, brands and logos used on this site are the property of their respective owners. The depiction, description or sale of products featuring these names, trademarks, brands and logos is for identification purposes only and is not intended to indicate any affiliation with or authorization by any rights holder.




100 Rate %
I haven't set up the buyer's impression yet. Please wait with me~
No comment

User discussion circle

Subscribe to get more info
Compare

1

You can also continue adding

2

You can also continue adding

3

You can also continue adding

4

You can also continue adding